Measurement-computing CB-COM-7021 Manuel d'utilisateur Page 56

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 76
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 55
56
CB-7021, CB-7022, CB-7024 Users Manual
2.23 $AA9N
Description: Read DA Configuration of Channel N
Note: The command is for CB-7022 only.
Syntax: $AA9N[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
9 Command for reading DA configuration
N Channel to read DA configuration (0 to 1)
Response: Valid Command: !AATS[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may not get
a response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
T Analog output type. See Sec. 1.10 for format.
S Analog output slew rate. See Sec. 1.10 for format.
Example:
Command: $0190 Receive: !0110
Read address 01 channel 0 DA configuration, returns 4 to 20
mA output and change immediate.
Related Command:
Sec. 2.24, $AA9NTS
Vue de la page 55