CB-7021, CB-7022, CB-7024 Users Manual
2.9 $AA1
Description: Perform 20 mA Calibration
Note: The command is for CB-7021/21P only.
Syntax: $AA1[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
1 command for performing 20 mA calibration
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $011 Receive: !01
Perform address 01 20 mA calibration, returns successful.
Related Command:
Sec. 2.8 $AA0, Sec. 2.10 $AA3VV
Related Topics:
Sec. 1.9 Calibration