CB-7021, CB-7022, CB-7024 Users Manual
2.13 $AA7
Description: Perform 10V Calibration
Note: The command is for CB-7021/21P only.
Syntax: $AA7[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
1 command for performing 10V calibration
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $017 Receive: !01
Perform address 01 10V calibration, returns successful.
Related Command:
Sec. 2.10 $AA3VV
Related Topics:
Sec. 1.9 Calibration