CB-7021, CB-7022, CB-7024 Users Manual
2.16 $AA0N
Description:
CB-7022: Perform 4 mA Calibration for Channel N
CB-7024: Perform 0 mA/-10V Calibration for Channel N
Note: The command is for CB-7022 and CB-7024 only.
Syntax: $AA0N[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
0 command for doing 4 mA (or 0 mA/-10V) calibration
N channel to calibrate (0 to 1 for CB-7022, 0 to 3 for CB-
7024)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: $0101 Receive: !01
Perform Address 01 channel 1 calibration (4 mA for CB-7022,
0 mA or -10.0V for CB-7024), returns successful.
Related Command:
Sec. 2.17 $AA1N, Sec. 2.18 $AA3NVV
Related Topics:
Sec. 1.9 Calibration