CB-7021, CB-7022, CB-7024 User’s Manual
CB-7022 Voltage Output Calibration Sequence:
1. Connect voltmeter to module’s voltage output.
2. Warm-Up for 30 minutes.
3. Set output type to 2. (0 to 10V) -> Refer Sec. 2.24.
4. Program output 10V. -> Refer Sec. 2.15.
5. Check the meter and trim the output for
10V match by using trim command.-> Refer Sec. 2.18.
6. Perform 10V Calibration Command. -> Refer Sec. 2.21.