36
CB-7021, CB-7022, CB-7024 User’s Manual
range, and the output is set to 20.0 mA.
Command: $022 Receive: !02300601
Read address 02 configuration, returns output type 0 to 20
mA, percent of span format, output change immediate.
Command: #02+050.00 Receive: >
Output address 02 value 50% (=10 mA), returns successful.
Command: $032 Receive: !02300602
Read address 03 configuration, returns output type 0 to 20
mA, hexadecimal format, output change immediate.
Command: #03800 Receive: >
Output address 03 value 0x800 (=10 mA), returns successful.
Related Command:
Sec. 2.1 %AANNTTCCFF, Sec. 2.2 $AA2
Related Topics:
Sec. 1.10 Configuration Tables, Sec. 3.5 Analog Output