CB-7080 & CB-7080D Counter/Timer User's Guide $AAAG
2-30
$AAAG
Description: Set gate control mode. Refer to "Gate control setting" for more information.
Syntax: $AAAG[chk](cr)
$ A delimiter character
AA 2-character HEX module address, from 00 to FF
G=0 Gate is low active
G=1 Gate is high active
G=2 Gate is disabled
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Response:
Valid response !AA[chk](cr)
Invalid response ?AA[chk](cr)
no response Syntax error, communication error or address error
! A delimiter character indicating a valid response
? A delimiter character indicating an invalid response
AA 2-character HEX module address
G=0 Gate is low active
G=1 Gate is high active
G=2 Gate is disabled
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Examples:
Module 1 gate is active low:
command: $01A0(cr)
response: !01(cr)
Module 2 gate is active high:
command: $02A1(cr)
response: !02(cr)
Module 3 gate is disabled (always active):
command: $03A2(cr)
response: !03(cr)