CB-7080 & CB-7080D Counter/Timer User's Guide %AANNTTCCFF
2-4
%AANNTTCCFF
Description: Set the configuration of a module.
Syntax: %AANNTTCCFF[chk](cr)
% A delimiter character.
AA Current 2-character HEX module address, from 00 to FF
NN New 2-character HEX module address, from 00 to FF
TT Input type code, refer to Table 1-10.
CC Baud rate code, refer to Table 1-8.
FF Status code, refer to Table 1-9.
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Response:
Valid response: !AA[chk](cr)
Invalid response: ?AA[chk](cr)
No response Syntax error, communication error or address error.
! A delimiter character indicating a valid response
? A delimiter character indicating an invalid response
AA 2-character HEX module address
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Examples:
The address of module 01 is configured to a new address 02, counter mode:
command: %0102500600(cr)
response: !02(cr)
Change to frequency mode:
command: %0202510600(cr)
response: !02(cr)