33
CB-7011/CB-7011D, CB-7018 Users Manual
2.12 $AA8
Description: Read LED Configuration
Note: The command is for CB-7011D/11PD only.
Syntax: $AA8[CHK](cr)
$ delimiter character
AA address of reading module (00 to FF)
8 command for setting LED configuration
Response: Valid Command: !AAV[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
V LED configuration
1=module control, 2=host control
Example:
Command: $018 Receive: !011
Read address 01 LED configuration, return module control.
Command: $028 Receive: !012
Read address 02 LED configuration, return host control.
Related Command:
$AA8V (Sec. 2.13), $AAZ(Data) (Sec. 2.18)