CB-7011/CB-7011D, CD-7018 Users Manual
2.1 %AANNTTCCFF
Description: Set module Configuration
Syntax: %AANNTTCCFF[CHK](cr)
% a delimiter character
AA address of setting module (00 to FF)
NN new address for setting module (00 to FF)
TT new type for setting module (Ref. Sec. 1.10)
CC new baudrate for setting module (Ref. Sec. 1.10)
FF new data format for setting module (Ref. Sec. 1.10)
When changing the baud rate or checksum, it is neces-
sary to short the INIT* pin to ground.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
A syntax error or communication error may yield no
response.
! delimiter for valid command
? delimiter for invalid command. If you change baud rate
or checksum setting without shorting INIT* to ground, the
module will return invalid command.
AA address of response module (00 to FF)
Example:
Command: %0102050600 Receive: !02
Change address from 01 to 02, return success.
Related Command:
$AA2 (Sec. 2.7)
Related Topics:
Configuration Tables (Sec. 1.10), INIT* pin Operation (Sec. 3.1)