Measurement-computing CB-7011 Manuel d'utilisateur Page 39

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 68
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 38
39
CB-7011/CB-7011D, CB-7018 Users Manual
2.18 $AAZ(Data)
Description: Set LED Data
Note: The command is for CB-7011D/11PD only.
Syntax: $AAZ(Data)[CHK](cr)
$ delimiter character
AA address of setting module (00 to FF)
Z command for setting LED data
(Data) data for show on the LED, from -19999. to +19999. The
data need sign, 5 digits and decimal point.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command or LED not set to host
control
AA address of response module (00 to FF)
Example:
Command: $01Z+123.45 Receive: !01
Send address 01 LED data +123.45, return success.
Command: $02Z+512.34 Receive: ?02
Send address 02 LED data +512.34, return the LED is not
setting in the host mode.
Related Command:
$AA8 (Sec. 2.12), $AA8V (Sec. 2.13)
Vue de la page 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 67 68

Commentaires sur ces manuels

Pas de commentaire