Measurement-computing CB-COM-7012 Manuel d'utilisateur Page 60

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 72
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 59
60
CB-7012, CB-7014, CB-7017 Users Manual
2.37 ~AA0
Description: Read Module Status
Syntax: ~AA0[CHK](cr)
~ Delimiter character
AA Address of module to read (00 to FF)
0 Command for module status
Response: Valid Command: !AASS[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
SS module status, 00=host watchdog status is clear, 04=host
watchdog status is set. The status is stored in EEPROM
and can only be reset by the ~AA1 command.
Example:
Command: ~010 Receive: !0100
Read Address 01 module status, return 00.
Command: ~020 Receive: !0204
Read Address 02 module status. A return of 04 means the
host watchdog timeout status is set.
Related Command:
Sec.2.38, ~AA1; Sec.2.40, ~AA3EVV
Related Topic:
Set.3.2, Module Status; Sec.3.3, Dual Watchdog Operation
Vue de la page 59
1 2 ... 55 56 57 58 59 60 61 62 63 64 65 ... 71 72

Commentaires sur ces manuels

Pas de commentaire