CB-7012, CB-7014, CB-7017 Users Manual
2.6 $AA1
Description: Perform Zero Calibration
Syntax: $AA1[CHK](cr)
$ Delimiter character
AA Address of module to set (00 to FF)
1 Command for performing zero calibration
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
Example:
Command: $011 Receive: !01
Perform Address 01 zero calibration, return successful.
Command: $021 Receive: ?02
Perform Address 02 zero calibration; returns calibration not
enabled before performing calibration command.
Related Command:
Sec. 2.5, $AA0; Sec. 2.18 ~AAEV
Related Topics:
Sec. 1.9 Calibration