Measurement-computing CB-7000 DIO Manuel d'utilisateur Page 41

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 68
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 40
41
CB-7000 DIO Manual
2.12 $AACN
Description: Clear Digital Input Counter
Command: $AACN[CHK](cr)
$ Delimiter character
AA Address of setting module (00 to FF)
C Command for clear digital input counter
N Digital counter channel N to clear
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid Command
? Delimiter for invalid Command
AA Address of response module(00 to FF)
Example:
Command: #010 Receive: !0100123
Read Address 01 input channel 0 counter value, return 123.
Command: $01C0 Receive: !01
Clear Address 01 input channel 0 counter value, return
successful.
Command: #010 Receive: !0100000
Read Address 01 input channel 0 counter value, return 0.
Related Command:
Sec. 2.4, #AAN
Note:
The Command is not for CB-7042/42D/43/43D/66/66D/67/67D.