6K-ERB08 User's Guide Installing the 6K-ERB08
Caution! Be careful not to pinch the cable when you replace the cover — if this cable is cut, the resulting
short circuit can damage the computer.
6.
7.
1.
2.
3.
4.
Connect the other end of the power cord to the connector labeled
PC POWER connector (P18) on the 6K-
ERB08.
Set the POWER IN jumper (JP1) for +5PC.
External +9V AC power adapter connections
You can power the 6K-ERB08 using the AC power adapter (MCC part number CB-PWR-9). This adapter
provides 9 volt, 1 amp DC power, 110 VAC power. To connect the AC adapter, do the following.
Turn off power to the computer.
Connect the CB-PWR-9 cable to the
9V EXTERNAL POWER connector (P19).
Plug the AC adapter into a power outlet.
Configure the POWER IN jumper (JP1) for 9V EXT.
Relay logic
Use jumper JP2 to select inverting or non-inverting logic to control the relays. Refer to for the
location of this jumper. The relay logic jumper is shown here configured for NON-INVERT (digital high). This
is the default position.
Figure 2-4
JP2
1
NON-INVERT
23
INVERT
Figure 2-6. Relay logic jumper JP2 (default position)
When set to non-invert, the relay activates when the DIO signal is high (1), and becomes inactive
(non-energized) when the DIO signal is low (0).
When set to
invert, the relay activates when the DIO signal is low (0), and becomes inactive
(non-energized) when the DIO signal is high (1).
Table 2-7
Table 2-7. Relay state and jumper position
summarizes the relay state in conjunction with the relay logic jumper setting.
JP2 position
Relay state
INVERT NON-INVERT
Active (energized) LO HI
Inactive (not-energized) HI LO
2-10