Measurement-computing WEB-TC Manuel d'utilisateur Page 31

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 36
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 30
WEB-TC User's Guide Specifications
31
Digital input/output
Table 6. Digital input/output specifications
Digital type
CMOS
Number of I/O
8 (DIO0 through DIO7)
Configuration
Independently configured for input or output.
Switch selectable output voltages: +5 V and +3.3 V
Power on conditions
Power on reset is Input mode except when bits are configured to operate as
alarms.
Pull-up/pull-down configuration
All pins are connected to 47 kOhm resistors that share a common point
accessible at Pin 22 of the device (PU/D). This pin is floating by default and is
user-configurable via external connection. For pull-up mode, connect this pin
to Pin 21 (+5V). For pull-down mode, connect this pin to Pin 48 (GND).
Digital I/O transfer rate (software paced)
Digital input 50 port reads or single bit reads per second typical.
Digital output 100 port writes or single bit writes per second typical.
Input high voltage (+5 V mode)
4 V min, 5.5 V absolute max.
Input high voltage (+3.3 V mode)
2.64 V min, 5.5 V absolute max.
Input low voltage (+5 V mode)
1 V max., -0.3 V absolute min.
Input low voltage (+3.3 V mode)
0.66 V max., -0.3 V absolute min.
Output low voltage (IOL = 2.5 mA)
0.6 V max.
Output high voltage (IOH=-2.5 mA)
4.3 V min. (+5 V mode), 2.7 V (+3.3 V mode)
Note 7: Ground pins on the WEB-TC labeled GND are isolated from AGND pins and from earth ground.
Temperature alarms
Table 7. Temperature alarm specifications
Number of alarms
8 (one per digital I/O line)
Alarm functionality
Each alarm controls its associated digital I/O line as an alarm output. The input to each
alarm may be any of the analog temperature input channels. When an alarm is enabled, its
associated I/O line is set to output and driven to the appropriate state determined by the
alarm options and input temperature. The alarm configurations are stored in non-volatile
memory and are loaded at power on.
Alarm input modes
Alarm when input temperature > T1
Alarm when input temperature > T1, reset alarm when input temperature goes below T2
Alarm when input temperature < T1
Alarm when input temperature < T1, reset alarm when input temperature goes above T2
Alarm when input temperature is < T1 or > T2
Note: T1 and T2 may be independently set for each alarm.
Alarm output modes
Disabled, digital I/O line may be used for normal operation
Enabled, active high output (digital I/O line goes high when alarm condition is met)
Enabled, active low output (digital I/O line goes low when alarm condition is met)
Alarm update rate
1 second
Memory
Table 8. Memory specifications
EEPROM
512 bytes for sensor configuration
FLASH
2 MB for device configuration and website storage
Microcontroller
Table 9. Microcontroller specifications
Type
One high-performance 8-bit RISC microcontroller (isolated)
One high-performance 16-bit RISC microcontroller (non-isolated)