4
p/n
1099-0901,
rev
2.0
958596
NDTRELAY2, Installation Guide
Specifications
Contact Outputs
Quantity 8
Type SPST, Normally Open
AC Rating 0.5 Amp @ 120 VAC Max.
DC Rating 1.0 Amp @ 30 VDC Max.
Approvals UL, CSA
Mechanical Life 5 Million Operations, Minimum
Electrical Life 100,000 Operations, Minimum at full-load
Digital Inputs
Quantity 4
Type TTL or Contact (weak pull-up)
Input Voltage High 4.00 V, Minimum
Input Voltage Low 0.8 V, Maximum
Event Counter
Quantity 1
Type TTL or Contact
Resolution 16 Bits
Communication Interface
RS232 Standard DB9S (Female)
Configuration 9600 Baud, 8-Bit Words, No Parity, 1 Start Bit
Power
Line Voltage, Input 85 to 265 VAC, 47 to 440 Hz
DC Power Out + 12 VDC @ 3.5 A max., via DIN 5 Power Connector
Operating Environment
Temperature 0 to 50°C
Humidity 0 to 95% RH, non-condensing
Commentaires sur ces manuels